10.8.4 CUSTOMER INTERFACES Terminals X1…X2
10.8.5 CUSTOMER INPUTS DRY PORTs: Terminal block X2
Connection of Remote Shut down facilities, Generator Operation, Customers specials
(see UM Section 9 / OPTIONS)
10.8.6 CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X1
Provision of signals for the automatic and orderly shutdown of servers, AS400 or Automation building systems
All voltage free contacts are rated 60 VAC max. and 500 mA max.:
All the interfaces are connected to Phoenix Spring terminals with wires : 0.5 mm2
(Function on request, to be defined)
(If connected , the battery charger current if depending of the battery
temp.)
(Do not remove the factory mounted bridge until external Remote Shut
down is connected)
Phoenix Spring Terminals (X1…X2) Connection