If there is not a heating demand for the analog
heat, and the discharge air temperature is
above 70F for more than 15 minutes, enable
the alarm.
If the active Zone Temperature is above the
active cooling setpoint for more than 15
minutes, enable the alarm.
Enable the airflow zeroing calculation.
If the communication between the damper
and the control board is not working, this will
be On.
Use as the network variable to send the AHU
fan status down to the box. Used when the
AHU does not use CXPro Tx modules.
When an input is used for a window contact,
shows the status if the window has been
opened.
Will be On if the heat is locked out.
If the damper cannot go to the desired
position, outside of the deadband.
Reverse the damper operation. On = Open is
CCW. Off = Open is CW.
Used for graphics. On when stage 3 heat is On
graphic_showPerimeterHeat
Used for graphics. On when
stagesOfPerimeterHeat (A75) is higher than 0.
graphic_variableFanEnable
Used for graphics. On when the variable fan
signal is above 0.
Used for graphics. On when stage 1 heat is On.
Used for graphics. On when stage 2 heat is On.
Enable the CO₂ signal to reset airflow
upwards. Can be disabled to prevent airflow
reset.
When the heartbeat communication is
enabled, and the heartbeat pulse has not been
toggled within the heartbeatTimer, enable the
alarm.
Reverse the operation of digital output DO12
When triggered, the damper will cycle
between the two stop points and recalculate
the 0 … 100% position based on them.
Point to toggle on and off when using the
digital heartbeat. Must be toggled within the
heartbeatTimer.
Enable heartbeat communication.