WIRING THE IO
Wiring the Universal Inputs
The FBVI-2U4-4T comes with 5 universal inputs. U/I-8 is dedicated to the internal airflow sensor. U/I-1
through U/I-4 is used for wiring in-room sensors, setpoint adjust, discharge air sensors, CO sensors,
relative humidity sensors, window, and motion sensors, depending on the application. The sequences
for this wide range of applications are available within the preloaded strategy.
U/I 1 will typically be where the room temperature sensor is wired. This input is pre-configured to
support a 10K Type III thermistor.
Note: Room sensors that short the thermistor for push-button occupancy are supported with this controller.
U/I 2 will typically be where the room setpoint adjusts is wired. This input is pre-configured to
support a 5K POT. It can also be set up for an occupancy sensor or window sensor.
U/I 3 is a dedicated input that has been configured to read a thermistor. In the pre-loaded
strategy, this input is used for a discharge air temperature sensor.
U/I 4 is configured as a voltage input. This input can be used for wiring in a CO sensor or relative
humidity sensor. It can also be set up for an occupancy sensor, window sensor, or a VAV fan
status.
Note: For CO or relative humidity sensors it must be a 0
10 Vdc sensor type. To change the span for the CO
sensor that is installed, adjust the following:
o minCO2Range (A278) Low range of the sensor.
o maxCO2Range (A280) High range of senor.
To adjust the span for the relative humidity sensor that is installed, adjust the following:
o minHumidityRange (A251) Low range of the sensor.
o maxHumidityRange (A305) High range of senor.
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button) occupancy, or window contact
(all optional)
UI-02
Setpoint Adjustment (optional 5K slider) occupancy, or window contact (all
optional)
UI-03
Discharge Temperature
UI-04
CO, Humidity, occupancy, fan status, or window contact (all optional)
UI-08
Flowrate Sensor