EasyManua.ls Logo

ABB FBVi-2U4-4T - Input; Output Points

ABB FBVi-2U4-4T
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FBVi-2U4-4T | FBVI-2U4-4T Contr
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
61
INPUT / OUTPUT POINTS
VAV Cooling Only 1-speed fan
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button) occupancy, or window
contact (all optional)
UI-02
Setpoint Adjustment (optional 5K slider) occupancy, or window contact (all
optional)
UI-03
Discharge Temperature
UI-04
CO
2
, Humidity, occupancy, fan status, or window contact (all optional)
UI-08
Flowrate Sensor
DO-09
DO-10
DO-11
DO-12
Series Fan Cmd
AO-14
AO-15
AO-16
Damper Control

Table of Contents

Related product manuals