INPUT CONFIGURATION
The inputs should be configured using the CXProHD BACnet commissioning tool. If changing the
configuration in the field, use these values.
For UI1 Configuration, set UI1Config (A173) analog setpoint to the following:
• 0 = Zone Temperature (default)
• 1 = Occupancy Sensor
• 2 = Window Sensor
For UI2 Configuration, set UI2Config (175) analog setpoint to the following:
• 0 = Temperature Offset 0-5K Ohm (default)
• 1 = Occupancy Sensor
• 2 = Window Sensor
For UI3 Configuration, set UI3Config (A176) analog setpoint to the following:
• 0 = Discharge Air Temperature (default)
• 1 = No discharge Air Temperature
For UI4 Configuration, set UI4Config (A174) analog setpoint to the following:
• 0 = CO₂ Sensor (default)
• 1 = Humidity Sensor
• 2 = Occupancy Sensor
• 4 = Window Sensor
• 5 = Fan Status