EasyManuals Logo

ABB FBVi-2U4-4T User Manual

ABB FBVi-2U4-4T
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
FBVi-2U4-4T | Control Sequence
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
90
NETWORK VARIABLES
There are network variables that are important to send information from the VAV to the AHU and from
the AHU to the VAV.
NETWORK IN VARIABLES
There are two methods to send information to the VAV from the AHU.
CXProHD BACnet Broadcast Module
o The AHU strategy should contain a BACNet Broadcast Tx Module with each of these
Broadcast names:
AHUFanStatus
AHUSupplyAir
OutsideAirTemp
netAHUMode
netOccCmd
GlobalShedCmd
BACnet Points
o BACnet point writes to the following variables:
netAHUFanStatus (D235)
netAHUSupplyAir (A304)
netOutdrAirTemp (A300)
HVACModeCmd (A287)
occCmd (A269)
netShedCmd (A310)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FBVi-2U4-4T and is the answer not in the manual?

ABB FBVi-2U4-4T Specifications

General IconGeneral
BrandABB
ModelFBVi-2U4-4T
CategoryDC Drives
LanguageEnglish

Related product manuals