FAN CONTROL
Parallel Variable Fan Speed Option
The variable fan speed will be controlled by modulating AO-15 (default 0
…
10 Vdc). The fan will run in
heating mode only. As the heating demand increases, the variable fan command will increase from
minFanSpeed (A237) to the maxFanSpeed (A238).
Series Variable Fan Speed Option
The variable fan speed will be controlled by modulating AO 15 (default 0
…
10 Vdc). In deadband mode,
the fan will run at a slower speed. As the heating demand increases, the variable fan command will
increase from minFanSpeed (A237) to the maxFanSpeed (A238). As the cooling demand increases, the
variable fan command will increase from minFanSpeed (A237) to maxFanSpeed (A238).