INPUT / OUTPUT POINTS
VAV Modulating HW Reheat with 1-speed fan AO-14 (0
10 Vdc)
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button) occupancy, or window
contact (all optional)
UI-02
Setpoint Adjustment (optional 5K slider) occupancy, or window contact (all
optional)
UI-03
Discharge Temperature
UI-04
CO
2
, Humidity, occupancy, fan status, or window contact (all optional)
UI-08
Flowrate Sensor
DO-09
DO-10
DO-11
DO-12
Series or Parallel Fan Cmd
AO-14
Stage 1 Modulating Heat
AO-15
AO-16
Damper Control
VAV Modulating HW Reheat with 1-speed fan Tri-state
IO POINTS
DESCRIPTION
UI-01
Zone Temperature (with optional override button) occupancy, or window
contact (all optional)
UI-02
Setpoint Adjustment (optional 5K slider) occupancy, or window contact (all
optional)
UI-03
Discharge Temperature
UI-04
CO
2
, Humidity, occupancy, fan status, or window contact (all optional)
UI-08
Flowrate Sensor
DO-09
Stage 1 Modulating Heat Valve Open
DO-10
Stage 1 Modulating Heat Valve Close
DO-11
DO-12
Series or Parallel Fan Cmd
AO-14
AO-15
AO-16
Damper Control