FBVi-2U4-4T | FBVi Operation
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
INPUTS AND OUTPUTS
Any of the UniPut terminals can be configured as an output.
INPUT MODES
Universal Input terminals and UniPut™ terminals can be configured as inputs in almost identical fashion:
Resistance measurement
Range: 0 ... 450 kΩ
Accuracy: ±0.5% of measured resistance
Temperature measurement
Range: -40 °C ... +110 °C
Accuracy: 10k NTC sensors (e.g. 10k Type 2 (10K3A1) or 10k Type 3 (10K4A1):
±0.3 °C, -40 to 90 °C (-40°F to 194°F); ±0.4 °C > 90 °C (194°F)
Pulse counting (volt-free)
up to 20 Hz, 25 ms – 25 ms
Analog Input
Range: 0 ... 10 V @ 130 kΩ
Accuracy: ±0.5% full scale [50mV]
Analog Input
Range: 0 ... 10 V @ 40 kΩ
Accuracy: ±0.5% full scale [50mV]
Pulse counting (0 … 10 V) up to 20 Hz, 25 ms – 25 ms
Current input
Range: 0 ... 20 mA
@ 390 Ω
Accuracy: ±0.5% full scale [100μA]
Current input
Range: 0 ... 20 mA
@ 390 Ω
Note: Current Input requires user-
supplied external 390 Ω
resistance.
Accuracy: depends on user supplied
external resistor
Note: Inputs use on-board 16-bit analog to digital convertor.
Note: All inputs and outputs are protected against short circuit, as well as over-voltage up to 24 V AC.