EasyManua.ls Logo

ABB FENA-01 - Page 109

ABB FENA-01
388 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus/TCP – Diagnostics 109
MODULE
Off There is no power applied to the device.
Flashing orange Device is attempting to obtain IP
configuration from the DHCP server.
Orange Device is executing Duplicate Address
Detection.
Flashing green Device is waiting for a Modbus request.
Green Device has received a Modbus request
within the Modbus/TCP Timeout period.
Flashing red Ethernet link is down.
Red Ethernet interface is disabled. Duplicate
Address Detection may have detected a
duplicate address. Check the IP
configuration and either initiate a
Fieldbus Adapter parameter refresh or
cycle power to the drive.
Flashing orange,
alternating with
the HOST
flashing orange
Internal file system error. The error may
be cleared by cycling drive power. If the
error persists, contact your local ABB
representative.
NETWORK
/NET
Off Ethernet link is down.
Flashing green Ethernet link is up at 100 Mbps.
Flashing indicates activity on interface.
Flashing orange Ethernet link is up at 10 Mbps.
Flashing indicates activity on interface.
Name Color Function

Table of Contents

Other manuals for ABB FENA-01

Related product manuals