EasyManua.ls Logo

ABB FENA-01 - (Group 2); FENA-01;-11;-21 Configuration Parameters - Group B

ABB FENA-01
388 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
258 PROFINET IO – Start-up
FENA-01/-11/-21 configuration parameters – group B (group 2)
Note: The actual parameter group number depends on the drive
type. Group B (group 2) corresponds to:
parameter group 55 in ACS355
parameter group 53 in ACSM1, ACS850 and ACQ810
parameter group 53 in ACS880 and ACS580 if the adapter is
installed as fieldbus adapter A or group 56 if the adapter is
installed as fieldbus adapter B.
No.
1)
Name/Value Description Default
01 DATA OUT 1
(master to drive)
Selects data word 1 received by the drive over
the PROFINET network. The content is defined
by a decimal number in the range of 0 to 9999
as follows:
See also Virtual address area allocation with
ACSM1 on page 261.
1 or 11
2)
ACS355:
FBA DATA OUT 1
ACSM1:
FBA DATA OUT1
ACS850/ACQ810:
FBA data out1
ACS880/ACS580:
FBA A/B data out1
0 = None Not used
1 = CW 16bit Control word (16 bits)
3)
2 = Ref1 16bit Reference REF1 (16 bits)
3)
3 = Ref2 16bit Reference REF2 (16 bits)
3)
11 = CW 32bit Control word (32 bits)
12 = Ref1 32bit Reference REF1(32 bits)
13 = Ref2 32bit Reference REF2 (32 bits)
21 = CW2 16bit Control word 2 (16 bits)
101…9999 Parameter index with format xxyy, where
xx is the parameter group number (1…99)
yy is the parameter number index within
that group (0199).
Note: In ACS880 and ACS580, choose Other
to display a list of mappable drive parameters.
0 Not used
1…99 Virtual address area of drive control
101…
9999
Parameter area of the drive

Table of Contents