118 EtherNet/IP – Start-up
03 COMM RATE Sets the bit rate for the Ethernet interface. 0 = Auto
ACS355:
FB PAR 3
ACSM1:
FBA PAR3
ACS850/ACQ810:
FBA par3
ACS880/ACS580:
Commrate
0 = Auto Autonegotiate
1 = 100 Mbps FD 100 Mbps, full duplex
2 = 100 Mbps HD 100 Mbps, half duplex
3 = 10 Mbps FD 10 Mbps, full duplex
4 = 10 Mbps HD 10 Mbps, half duplex
04 IP
CONFIGURATION
Sets the method for configuring the IP address,
subnet mask and gateway address for the
adapter module.
1 = Dyn
IP DHCP
ACS355:
FB PAR 4
ACSM1:
FBA PAR4
ACS850/ACQ810:
FBA par4
ACS880/ACS580:
IP configuration
0 = Static IP Configuration will be obtained from parameters
0513.
1 = Dyn IP DHCP Configuration will be obtained via DHCP.
05 IP ADDRESS 1 An IP address is assigned to each IP node on a
network. An IP address is a 32-bit number that
is typically represented indotted decimal
notation consisting of four decimal integers, on
the range 0…255, separated by periods. Each
integer represents the value of one octet (8-
bits) in the IP address. Parameters 0508
define the four octets of the IP address.
0
ACS355:
FB PAR 5
ACSM1:
FBA PAR5
ACS850/ACQ810:
FBA par5
ACS880/ACS580:
IP address 1
0…255 IP address
……
No. Name/Value Description Default