PROFINET IO – Start-up 265
5106 FB PAR 6
(IP ADDRESS 2)
168
2)
Second part of the IP address
5107 FB PAR 7
(IP ADDRESS 3)
0
2)
Third part of the IP address
5108 FB PAR 8
(IP ADDRESS 4)
16
2)
Last part of the IP address
5109 FB PAR 9
(SUBNET CIDR)
24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
3018 COMM FAULT
FUNC
3 = LAST SPEED
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT
TIME
3.0 s
2)
Defines the fieldbus communication
break supervision time.
5401 FBA DATA IN 1 4 (= SW 16bit)
1)
Status word
5402 FBA DATA IN 2 5 (= Act1 16bit)
1)
Actual value 1 (speed)
5403 FBA DATA IN 3 106
2)
Power
5404 FBA DATA IN 4 107
2)
DC bus voltage
5501 FBA DATA OUT 1 1 (= CW 16bit)
1)
Control word
5502 FBA DATA OUT 2 2 (= Ref1 16bit)
1)
Reference 1 (speed)
5503 FBA DATA OUT 3 1202
2)
Constant speed 1
5504 FBA DATA OUT 4 1203
2)
Constant speed 2
5127 FBA PAR
REFRESH
1 = REFRESH Validates the FENA-01/-11/-21
configuration parameter settings.
1001 EXT1
COMMANDS
10 = COMM Selects the fieldbus interface as the
source of the start and stop
commands for external control
location 1.
1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1 as
the source for speed reference 1.
1601 RUN ENABLE 7 = COMM Selects the fieldbus interface as the
source for the inverted Run enable
signal (Run disable).
Drive parameter Setting for ACS355
drives
Description