52 Modbus/TCP Start-up
03 COMM RATE Sets the bit rate for the Ethernet interface. 0 = Auto
ACS355:
FB PAR 3
ACSM1:
FBA PAR3
ACS850/ACQ810:
FBA par3
ACS880/ACS580:
Commrate
0 = Auto Autonegotiate
1 = 100 Mbps FD 100 Mbps, full duplex
2 = 100 Mbps HD 100 Mbps, half duplex
3 = 10 Mbps FD 10 Mbps, full duplex
4 = 10 Mbps HD 10 Mbps, half duplex
04 IP
CONFIGURATION
Sets the method for configuring the IP address,
subnet mask and gateway address for the
module.
1 = Dyn
IP DHCP
ACS355:
FB PAR 4
ACSM1:
FBA PAR4
ACS850/ACQ810:
FBA par4
ACS880/ACS580:
IP configuration
0 = Static IP Configuration will be obtained from parameters
0513.
1 = Dyn IP DHCP Configuration will be obtained via DHCP.
05 IP ADDRESS 1 An IP address is assigned to each IP node on a
network. An IP address is a 32-bit number that
is typically represented in “dotted decimal
notation consisting of four decimal integers, on
the range 0…255, separated by periods. Each
integer represents the value of one octet (8-
bits) in the IP address. Parameters 05...08
define the four octets of the IP address.
0
ACS355:
FB PAR 5
ACSM1:
FBA PAR5
ACS850/ACQ810:
FBA par5
ACS880/ACS580:
IP address 1
0…255 IP address
……
No. Name/Value Description Default