Modbus/TCP – Start-up  79
50.03 FBA A comm loss t 
out
3.0 s
2)
Defines the fieldbus A 
communication break supervision 
time.
50.04 FBA A ref1 type 4 = Speed Selects the fieldbus A reference 1 
type and scaling.
51.01 FBA A type 128 = ETHERNET
1)
Displays the type of the fieldbus 
adapter module.
51.02 Protocol/Profile 1 = MB/TCP ABB E Selects the Modbus/TCP protocol 
and the ABB Drives - Enhanced 
profile.
51.03 Commrate 0 = Auto
2)
Ethernet communication rate is 
negotiated automatically by the 
device.
51.04 IP configuration 0 = Static IP
2)
Configuration will be obtained 
from parameters 05…13.
51.05 IP address 1 192
2)
First part of the IP address
51.06 IP address 2 168
2)
Second part of the IP address
51.07 IP address 3 0
2)
Third part of the IP address
51.08 IP address 4 16
2)
Last part of the IP address
51.09 Subnet CIDR 24
2)
Sets the network mask as 
255.255.255.0, allowing access 
only to the last subnet.
51.20 Timeout time 10
2)
Sets the communication timeout 
as 1 second.
51.21 Timeout mode 2 = Control RW
2)
The timeout feature monitors the 
updating of the Control word and 
Reference 1.
52.01 FBA A data in1 01.14
2)
Output power
52.03 FBA a data in3 01.11
2)
DC voltage
53.01 FBA A data out1 22.26
2)
Constant speed 1
53.03 FBA A data out3 22.27
2)
Constant speed 2
51.27 FBA A par refresh 1 = Refresh Validates the FENA-11/-21 
configuration parameter settings.
Drive parameter Setting for ACS880 
drives
Description