90  Modbus/TCP – Communication profiles       
7 ALARM 1 Warning/Alarm
0 No warning/alarm
8AT_
SETPOINT
1 OPERATION. Actual value equals reference 
(= is within tolerance limits, ie, in speed 
control, speed error is 10% max. of nominal 
motor speed).
0 Actual value differs from reference (= is 
outside tolerance limits.)
9 REMOTE 1 Drive control location: REMOTE (EXT1 or 
EXT2)
0 Drive control location: LOCAL
10 ABOVE_
LIMIT
1 Actual frequency or speed equals or exceeds 
supervision limit (set by drive parameter). 
Valid in both directions of rotation.
0 Actual frequency or speed within supervision 
limit
11 EXT_CTRL_
LOC
1 External Control Location EXT2 selected.
Note concerning ACS880: This bit is 
effective only if the fieldbus interface is set as 
the target for this signal by drive parameters. 
User bit 0 selection (06.33)
0 External Control Location EXT1 selected
12 EXT_RUN_
ENABLE
1 External Run Enable signal received.
Note concerning ACS880: This bit is 
effective only if the fieldbus interface is set as 
the target for this signal by drive parameters. 
User bit 1 selection (06.34)
0 No External Run Enable signal received
13…
14
Reserved or freely programmable status bits
(Not supported with ACS355)
15 FBA_ERROR 1 Communication error detected by fieldbus 
adapter module
0 Fieldbus adapter communication OK
Bit Name Value STATE/Description