KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
104
room can be maintain with a forced operation. However, for this the system and/or
actuator must have "Forced operation" function.
12.34.8 General – Additional functions / objects
Options No
Yes
– This parameter enables additional functions and communication objects.
Single / master / Slave:
- RTC controller On/Off
- Send fault actual temperature
- Window contact
- Presence detector
- Controller status RHCC
- Controller status HVAC
- Units switchover Celsius (°C) or Fahrenheit (°F)
Single / Master:
- Set basic setpoint by group object
Slave:
- RTC condensate water alarm
12.34.9 General – Delay time for read telegrams after reset (s)
Options Time input from 1 sec to 255 sec
A delay in reading additional functions / objects after the reset of device
12.34.10 Operating functions – Temperature unit
Options °C
°F
This is where the temperature unit is select to be display on the device. The parameter is
use to choose between Celsius (°C) and Fahrenheit (°F).
12.34.11 Operating functions – Hide temperature unit
Options No
Yes
To select whether to display or not to display the temperature unit on the RTC LCD main
display
12.34.12 Operating functions – Switchover heating / cooling
Options No
Yes