KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
129
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on “Heating”,
“Heating with additional stage”, "Heating and cooling" or "Heating and cooling with
additional stages", only available when "Setpoint heating comfort = Setpoint cooling
comfort" parameter is set on "No".
Specifies the comfort temperature for heating when people are present.
12.34.77 Setpoint setting – Reduction for standby heating (°C)
Options Input from 0 to 15
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on “Heating”,
“Heating with additional stage”, "Heating and cooling" or "Heating and cooling with
additional stages".
Specifies the temperature in heating mode when nobody is present. On devices with a
display, this mode is indicated by the standby symbol.
12.34.78 Setpoint setting – Reduction for ECO heating (°C)
Options Input from 0 to 15
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on “Heating”,
“Heating with additional stage”, "Heating and cooling" or "Heating and cooling with
additional stages".
Specifies the temperature in heating mode when nobody is present. On devices with a
display, this mode is indicated by the ECO symbol.
12.34.79 Setpoint setting – Setpoint temperature for frost protection (°C)
Options Input from 5 to 15