KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
55
– 1 byte 0 - 100%: percentage values (0 = 0%, 255 = 100%)
– 1 byte 0 - 255: arbitrary values from 0 to 255
– 2-byte float: floating point value (physical values such as temperature or brightness) -
671088.64 to 671088.64
– 2-byte signed: arbitrary values from -32768 to +32767
– 2-byte unsigned: arbitrary values from 0 to 65,535
– 4-byte float: floating point value (physical values) -4000000 to 4000000
– 4-byte signed: arbitrary values from -2147483648 to 2147483647
– 4-byte unsigned: arbitrary values from 0 to 4294967295
12.14.6 Objects no
Switching 1 actuator 1 bit DPT 1.001 C, W, T
Switching 1 actuator 1 byte DPT 5.001 C, W, T
Switching 1 actuator 2 byte DPT 9.xxx C, W, T
Switching 1 actuator 2 byte DPT 7.001 C, W, T
Switching 1 actuator 4 byte DPT 13.001 C, W, T
Switching 1 actuator 4 byte DPT 12.001 C, W, T
Switching 2 actuator 1 byte DPT 5.001 C, W, T
Switching 2 actuator 2 byte DPT 9.xxx C, W, T
Switching 2 actuator 4 byte DPT 14.xxx C, W, T
Switching 2 actuator 4 byte DPT 12.001 C, W, T
Switching 3 actuator 1 byte DPT 5.001 C, W, T
Switching 3 actuator 1 byte DPT 5.010 C, W, T
Switching 3 actuator 2 byte DPT 8.001 C, W, T
Switching 3 actuator 4 byte DPT 14.xxx C, W, T
Switching 3 actuator 4 byte DPT 12.001 C, W, T
Switching 4 actuator 1 bit DPT 1.001 C, W, T
Switching 4 actuator 1 byte DPT 5.010 C, W, T
Switching 4 actuator 2 byte DPT 8.001 C, W, T
Switching 4 actuator 4 byte DPT 13.001 C, W, T