12.32.4 Extended parameter – Group object value
Options Normal
Inverse
Note: This object is only adjustable if the "Enable object" parameter is set to
"activated".
The enable function normally functions as follows:
The function is active if an ON telegram is receive on the 1-bit communication object
"Enable". The function is block if an OFF telegram is receive on the 1-bit communication
object "Enable".
Via the parameter "Logic of the enable function", the above-described behavior can be
reversed, i.e. if an ON telegram is received on the 1-bit communication object "Enable",
the function is blocked. The function is active if an OFF telegram is receive on the 1-bit
communication object "Enable".
12.32.5 Extended parameter – Enable group object after return of voltage
Options No
Yes
Note: This object is only adjustable if the "Enable object" parameter is set to
"activated".
The parameter "Enable after return of voltage" exists to permit a defined behavior at the
"Enable" communication object after a return of bus voltage. A determination is made
here about whether a "1" ("enable") or a "0" ("blocked") is present on the enable object
after the return of bus voltage.
Note: If the logic of the enable function is set to "inverse", the behavior is also inverted
after the return of bus voltage, i.e. if the parameter "enable after return of bus voltage" is
set to "enable", and at the same time the "logic of the enable function" is parameterized
to "inverse", then the function will initially not be active after return of bus voltage. This
must first be activate via the receipt of an OFF telegram on the enable object.
12.32.6 Extended parameter – Input monitoring
Options Deactivate
Activate
Should there the upper or lower threshold value be exceeded (i.e. above the upper limit
or below the lower limit) during the blocking, the relevant output telegrams are sent out

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX Yucus YUB/U1.0.1 Series and is the answer not in the manual?

ABB i-bus KNX Yucus YUB/U1.0.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX Yucus YUB/U1.0.1 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals