Action
Tap Update.
A dialog box is displayed, warning that the updating operation cannot be undone:
• Tap Update to proceed with updating the revolution counters.
• Tap Cancel to cancel updating the revolution counters.
Tapping Update and a confirmation window is displayed.
8
Tap OK.9
The revolution counter for the selected axes is updated.
CAUTION
If a revolution counter is incorrectly updated, it will cause incorrect manipulator posi-
tioning, which in turn may cause damage or injury!
Check the synchronization position very carefully after each update. See Checking
the synchronization position on page 305.
10
286 Product manual - IRB 1010
3HAC081964-001 Revision: B
© Copyright 2022 ABB. All rights reserved.
6 Calibration
6.3.1 Updating revolution counters on OmniCore robots
Continued