LMT100 AND LMT200 | MAGNETOSTRICTIVE LEVEL TRANSMITTERS | FF OI/LMT100/200/FF-EN REV. A
23
Figure 22 Remote version: connecting the signal cable
Terminal Color / function
VDD Yellow
/M/R White
GND Green
HS Pink
DX Gray
RX Brown
Ground terminal (functional ground / shield)
NOTICE
The shielding of the signal cable also serves as a functional
ground and must be connected to the sensor and to the
transmitter on both sides.
1 Use the signal cable connected to the transmitter to make
the electrical connection between the measuring sensor and
the transmitter.
2 Unscrew the cover of the terminal boxes on the transmitter
and the measuring sensor.
3 Tailor the signal cable in accordance with specification.
4 Insert the cable through the cable gland into the terminal
box.
5 Tighten the cable gland.
6 Connect the wires to the corresponding terminals (refer
figure 22).
7 Connect the shield of the signal cable to the forked cable lug
to the ground terminal.
8 Screw on the cover of the terminal compartment on the
transmitter and the measuring sensor and tighten by hand.
Make sure the gaskets for the cover are seated properly.