LST300 | COMPACT ULTRASONIC LEVEL TRANSMITTER | LST300–EN REV. E
47
8 Click Generate to generate the linearization table for this channel shape.
9 The linearization table is displayed below.
10 Click Store user curve to device
to store the linearization table to the device.
11 Click Calibration > Linearization > Linearization to confirm the setting.
12 Click Load user curve from device and select
Enable
in the Linearization Status field to active the open channel flow function.