20 LST300 | COMPACT ULTRASONIC LEVEL TRANSMITTER | LST300EN REV. E
5 Commissioning
Figure 21
B Blanking
E Empty
F Full
D Distance
L Level
Preliminary checks prior to start-up
Before beginning the commissioning procedure, ensure:
The power supply is OFF.
The power supply is within the specified range (12 to 42 V DC).
The pin assignment matches the connection diagram.
The transmitter is correctly grounded.
The transmitter is within temperature limits.
The transmitter is installed in a location free of vibration.
The terminal cover is sealed.
Commissioning using the Easy Setup menu
The most common configuration parameters are summarized
in the Easy Setup menu. This menu provides the quickest way
to configure the device.
For a detailed description of these menus and parameters, see
section “Parameter descriptions”.
1 Log on to the LST300 at the Standard or Advanced level.
2 Select Easy Setup in the main menu.
3 Select a language in the “Easy Setup” menu and press .
4 Select an option of Operation Mode in the “Easy Setup”
menu and press
.

Table of Contents