LST300 | COMPACT ULTRASONIC LEVEL TRANSMITTER | LST300EN REV. E
IMPORTANT (NOTE)
“F8” digit means that customers choose FM US or FM C Non
incendive or Intrinsically Safe method of protection on the
product.
Dedicated check box is to be marked by the manufacturer or
customers.
IMPORTANT (NOTE) – Note for transmitter with combined
approval
Before installation of the transmitter, customers should
permanently mark their chosen Protection Concept on the
safety label. The transmitter can only be used according to this
Protection Concept for the whole life.
If two or more types of protection box (on the safety label) are
permanently marked, the transmitter must be removed from
hazardous classified locations.
The selected Type of Protection is allowed to be changed only
by the manufacturer after a new satisfactory assessment.
NEPSI approval design for China (Non Sparking)
For detailed information, refer to section “Meter design for
NEPSI non sparking, ATEX/IECEx energy limited (Zone 2 /22),
cFMus division 2, Zone 2/22.
NEPSI approval design for China (Intrinsically Safe)
GYJXXXXXX
For detailed information, refer to section “Meter design for
NEPSI intrinsic safety, ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20.
EC type-examination certificate FM15ATEX0064X
Designation:
II 3 G Ex nA IIC T6...T4 Gc - II 3 D Ex tc IIIC T85°C
For electrical parameters, refer to cert, FM15ATEX0064X
For detailed information, refer to section “Meter design for
NEPSI non sparking, ATEX/IECEx energy limited (Zone 2 /22),
cFMus division 2, Zone 2/22.
Certificate of conformity IECEx FME 15. 0010X
Designation:
Ex nA IIC T6...T4 Gc - Ex tc IIIC T85°C
For electrical parameters, refer to cert, IECEx FME 15.0010X
For detailed information, refer to section “Meter design for
NEPSI non sparking, ATEX/IECEx energy limited (Zone 2 /22),
cFMus division 2, Zone 2/22.
EC type-examination certificate FM15ATEX0063X
Designation:
II 1 G Ex ia IIC T6...T4 Ga - II 1 D Ex ia IIIC T85° C
For electrical parameters, refer to cert, FM15ATEX0063X
For detailed information, refer to section “Meter design for
NEPSI intrinsic safety, ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20.
Certificate of conformity IECEx FME 15. 0010X
Designation:
Ex ia IIC T6...T4 Ga - Ex ia IIIC T85° C
For electrical parameters, refer to cert, IECEx FME 15.0010X
For detailed information, refer to section “Meter design for
NEPSI intrinsic safety, ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20.
FM approval design for the USA and Canada (Non Incendive)
CL I, ZONE 2 AEx/Ex nA IIC T6...T4
CL I/DIV 2/GP ABCD
NI CL I/DIV 2/GP ABCD
DIP CL II, III/DIV 2/GP EFG
For detailed information, refer to section “Meter design for
NEPSI non sparking, ATEX/IECEx energy limited (Zone 2 /22),
cFMus division 2, Zone 2/22.
FM approval design for the USA and Canada (Intrinsically
Safe)
IS/Sec. Intrinseque (Entity) CL I
ZONE 0 AEx/Ex ia IIC T6...T4
CL I/DIV 1/GP ABCD IS - CL II,III DIV 1/GP EFG
IS Control Drawing number: 3KXL065035U0009
For detailed information, refer to section “Meter design for
NEPSI intrinsic safety, ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20.