56
AUTOMATIC CONTROL UNIT, OMD800
Register Address R/W Values
REG_SLAVE_ID 500 R Fixed value 49
REG_SW_VERSION
501
R
Bits 8-15 = SW Version number in ASCII
format
Bits 0-7 = SW Version letter in ASCII format
REG_OPERATION_COUNTER 502 R Number of switch position transitions
REG_SERIAL_NUMBER_0 560 R Serial number digit 0
REG_SERIAL_NUMBER_1 561 R Serial number digit 1
REG_SERIAL_NUMBER_2 562 R Serial number digit 2
REG_SERIAL_NUMBER_3 563 R Serial number digit 3
REG_SERIAL_NUMBER_4 564 R Serial number digit 4
REG_SERIAL_NUMBER_5 565 R Serial number digit 5
REG_SERIAL_NUMBER_6 566 R Serial number digit 6
REG_SERIAL_NUMBER_7 567 R Serial number digit 7
REG_OPERATING_MODE
600
R/W
0 = Local
1 = Remote
REG_ADDRESS 604 R/W 1...247
REG_BAUD_RATE
605
R/W
0 = 9600
1 = 19200
2 = 38400
REG_PROTOCOL
606
R/W
0 = Even parity / 8 data bits / 1 stop bit
1 = Odd parity / 8 data bits / 1 stop bit
2 = No parity / 8 data bits / 1 stop bit
3 = Even parity / 8 data bits / 2 stop bits
4 = Odd parity / 8 data bits / 2 stop bits
5 = No parity / 8 data bits / 2 stop bits
REG_TAG_NAME_0 607 R/W Letter 0 in ASCII format
REG_TAG_NAME_1 608 R/W Letter 1 in ASCII format
REG_TAG_NAME_2 609 R/W Letter 2 in ASCII format
REG_TAG_NAME_3 610 R/W Letter 3 in ASCII format
REG_TAG_NAME_4 611 R/W Letter 4 in ASCII format
REG_ DEVICE_STATUS
622
R/W
0 = Auto
1 = Manual
2 = Test
3 = Powersave
REG_LN1_PHASES
623
R/W
0 = 1 phase
1 = 3 phases without N
2 = 3 phases with N
REG_ RATED_VOLTAGE
624
R/W
0 = 100/57 V
1 = 115/66 V
2 = 120/70 V
3 = 208/120 V
4 = 220/127 V
5 = 230/132 V
6 = 240/138 V
7 = 277/160 V
8 = 347/200 V
9 = 380/220 V
10 = 400/230 V
11 = 415/240 V
12 = 440/254 V
13 = 480/277 V