EasyManua.ls Logo

ABB Pluto Series - 4 Gateway Default Configuration; 4.1 Gateway Configuration; 4.2 Commissioning

ABB Pluto Series
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 2TLC172011M0205_B
4 Gateway Default Configuration
4.1 Gateway Configuration
The Pluto gateway default configuration is very limited. The configuration is done on the gateway
by setting switch 1-2 of the DIP switch SW2. When this can be used is listed in the table below.
DIP-switch
1 2
Description
0 0 Only to read status from Pluto station 0 and 1.
0 1 Only to read status from Pluto station 0 – 7.
1 0 Only to read status from Pluto station 0 – 15.
1 1 Only to read status from Pluto station 0 – 31.
This configuration is current not possible to use because of limitations in the I/O
size in the ABB robotic system.
Note:
The ABB robotic system can with the “default” configuration mode only read data from
the connected Pluto system.
To be able to write data to the Pluto system you can’t use the “default” configuration
mode.
If the Pluto system has any Pluto with station number above 15 the “default”
configuration mode can’t be used.
4.2 Commissioning
During commissioning;
At ABB robotic system start it will do a DeviceNet IO connection with the gateway.
If the MNS LED is steady green the gateway is connected and normal operation.

Related product manuals