Parameters 45
Power level 70% Relay output activation when output power level
over 70% of rated power.
8
114.14 DIO2 configuration (Visible only when parameter 114.0 1 Option
module 1 type is FIO-01 or FIO-11.)
Selects whether DIO2 of the extension module is
used as a digital input or output.
Input
Output DIO2 is used as a digital output. 0
Input DIO2 is used as a digital input. 1
114.16 DIO2 output source (Visible only when parameter 114.01 Option
module 1 type is FIO-01 or FIO-11.)
Selects an inverter signal to be connected to
digital input/output DIO2 of the extension module
when parameter 114.14 DIO2 configuration is set
to Output. For the available selections, see
parameter 114.11 DIO1 output source.
Off
114.19 DIO3 configuration (Visible only when parameter 114.0 1 Option
module 1 type is FIO-01.)
Selects whether DIO3 of the extension module is
used as a digital input or output.
No action
Output DIO3 is used as a digital output. 0
Input DIO3 is used as a digital input. 1
114.21 DIO3 output source (Visible onlt when parameter 114.01 Option
module 1 type is FIO-01.)
Selects an inverter signal to be connected to
digital input/output DIO3 of the extension module
when parameter 114.19 DIO3 configuration is set
to Output. For the available selections, see
parameter 114.11 DIO1 output source.
Off
114.24 DIO4 configuration (Visible only when parameter 114.0 1 Option
module 1 type is FIO-01.)
Selects whether DIO4 of the extension module is
used as a digital input or output.
Input
Output DIO4 is used as a digital output. 0
Input DIO4 is used as a digital input. 1
114.26 DIO4 output source (Visible only when parameter 114.01 Option
module 1 type is FIO-01.)
Selects an inverter signal to be connected to
digital input/output DIO4 of the extension module
when parameter 114.24 DIO4 configuration is set
to Output. For the available selections, see
parameter 114.11 DIO1 output source.
Off
114.26 AI1 actual value (Visible only when parameter 114.01 Option
module 1 type is FIO-11.)
Displays the value of analog input AI1 in mA or V
(depending on whether the input is set to current
or voltage). This parameter is read-only.
-
No. Name/Value/Range Description Default
FbEq (16b/32b)