110 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. 888-385-1221 www.abb-control.com
No Type Parameter Description Ran
g
eUnit
34 Read/Write PTC Op Type of operation for PTC protection Stop M, Stop A, Ind
35 Read/Write Ext ByPass External By-pass contactor is used No, Yes
36 Read/Write BP Fault Op
Type of operation for by-pass monitor
protection
Stop M, Stop A
37 Read/Write Warn I=High High current warning No, Yes
38 Read/Write Wa I=H Lev Trip level for high current warning 0.5 5.0 x Ie
39 Read/Write Warn I=Low Low current warning No, Yes
40 Read/Write Wa I=L Lev Trip level for low current warning 0.4 1.0 x Ie
41 Read/Write Warn OL Overload warning No, Yes
42 Read/Write Wa OL Lev Trip level for overload warning 40 99 %
43 Read/Write Warn SCR OL SCR overload warning No, Yes
44 Read/Write Ph Loss Op Type of operation for phase loss fault Stop M, Stop A
45 Read/Write FB Fault Op Type of operation for fieldbus fault Stop M, Stop A
46 Read/Write Freq F Op. Type of operation for frequency fault Stop M, Stop A
47 Read/Write HS Temp Op
Type of operation for heat sink over
temperature fault
Stop M, Stop A
48 Read/Write SCR SC Op
Type of operation for SCR short circuit
fault
Stop M, Stop A
49 Read In0 Function of programmable input In0
None, Reset, Enable,
Jo
, DOL-on, Start2
50 Read In1 Function of programmable input In1
None, Reset, Enable,
Jog, DOL-on, Start3
51 Read/Write Relay K4
Function of programmable relay output
K4
Run, TOR, Event
52 Read/Write Relay K5
Function of programmable relay output
K5
Run, TOR, Event
53 Read/Write Relay K6
Function of programmable relay output
K6
Run, TOR, Event
54 Read/Write SW Outp V7
Function of programmable software
output V7
Run, TOR, Event
55 Read/Write Event K4
Different events to include for
signalling with K4 if Event is selected
0 65535, Bit mask see
separate description.
56 Read/Write Event K5
Different events to include for
signalling with K5 if Event is selected
0 65535, Bit mask see
separate description.
57 Read/Write Event K6
Different events to include for
signalling with K6 if Event is selected
0 65535, Bit mask see
separate description.
58 Read/Write Event V7
Different events to include for
signalling with V7 if Event is selected
0 65535, Bit mask see
separate description.
59 Read Fieldb Ctrl Control of the softstarter with fieldbus No, Yes
60 Read Fieldb Type Type of fieldbus AS-I, Other
61 Read Fieldb Addr Fieldbus address 0 1000
Chapter 8 - Fieldbus communication (option)