Low Voltage Products & Systems 111
ABB Inc. 888-385-1221 www.abb-control.com AC 1006.9 - 5/03
No Type Parameter Description Ran
g
eUnit
62 Read/Write No of Seq
Number of sequences for sequence
start.
No, 2, 3
63 Read/Write Start Ramp1 1st sequence, time for start ramp 1 120 Sec
64 Read/Write Init Volt1
1st sequence, initial voltage for start
ramp
30 70 %
65 Read/Write Curr Lim1 1st sequence, current limit 2.0 5.0 x Ie
66 Read/Write 1st Set Ie 1st sequence, motor rated current 0 3000 (*) Amp
67 Read/Write Start Ramp2 2nd sequence, time for start ramp 1 120 Sec
68 Read/Write Init Volt2
2nd sequence, initial voltage for start
ramp
30 70 %
69 Read/Write Curr Lim2 2nd sequence, current limit 2.0 5.0 x e
70 Read/Write 2nd Set Ie 2nd sequence, motor rated current 0 3000 (*) Amp
71 Read/Write Start Ramp3 3rd sequence, time for start ramp 1 120 Sec
72 Read/Write Init Volt3
3rd sequence, initial voltage for start
ramp
30 70 %
73 Read/Write Curr Lim3 3rd sequence, current limit 2.0 5.0 x Ie
74 Read/Write 3rd Set Ie 3rd sequence, motor rated current 0 3000 (*) Amp
75 Read Language Language to use on display
US/UK, FI, SE, PT, NL,
IT, FR, ES, DE, CN
76 Read Dummy 76 Spare parameter 0
77 Read LCD Auto Off Time for display automatic turn-off 1 255 Sec
78 Read Password Password for display 0 255
79 Read Date Type Type of date presentation ISO , CE , US
80 Read Date Year Year 2001 2060
81 Read Date Month Month 1 12
82 Read Date Day Day 1 31
83 Read Time Hour Hour 0 23
84 Read Time Min Minutes 0 59
85 Read S Port Ctrl Serial port control No, Yes
86 Read S Port Addr1 Address of service port 1st digit 0 255
87 Read S Port Addr2 Address of service port 2nd digit 0 255
88 Read S Port Addr3 Address of service port 3rd digit 0 255
89 Read S Port Addr4 Address of service port 4th digit 0 255
90 Read CT Ratio Ir Ratio of current transformers 0 2500
91 Read Int ByPass Built-in by-pass contactor No, Yes
92 Read ByPass AC3 AC3 value of built-in by-pass contactor 0 2500 Amp
93 Read SOP1 SCR Parameter 1 0.7 1.2
94 Read SOP2 SCR Parameter 2 0.05 20.00
95 Read SOP3 SCR Parameter 3 0.011 1.200
96 Read SOP4 SCR Parameter 4 1.0 20.0