Low Voltage Products & Systems 163
ABB Inc. 888-385-1221 www.abb-control.com AC 1006.9 - 5/03
Status Possible cause
The fieldbus communication is not
working.
Check that the fieldbusplug is
connected correctly.
Check that the correct type of
fieldbusplug is used.
Check that the parameter
Fieldbus
Type
is set according to the present
fieldbus t
y
pe.
An internal communication fault of
the softstarter has occurred.
Disconnect and reconnect the
control voltage (U
s
) and make a
restart.
If the same fault remains, contact
your ABB sales office.
Fieldbus fault
Internal faults
Solution
Chapter 11 - Troubleshooting
Power on ProtectionFault
Fault EB Timeout
Reset Back
Power on ProtectionFault
Fault Intern 1
Reset Back
Power on ProtectionFault
Fault Intern 2
Reset Back
Power on ProtectionFault
Fault Intern 3
Reset Back
Power on ProtectionFault
Fault Intern 4
Reset Back