166 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. 888-385-1221 www.abb-control.com
Status Possible cause
PTC protection Check that the PTC circuit is closed
and that the inputs are connected.
Check and correct the reason for
the overheating
Check and correct the reason for
the overheating
SCR overload protection Check and replace the softstarters
with one of a suitable size.
Check and decrease number of
starts / hour.
Check that current limit level is not
set too low.
Check that the ramp time for start is
not too long.
Solution
An over-temperature is detected
by the PTC thermistors in the
motor.
The softstarter is too small.
Too many starts / hour.
The ramp time for start is too long.
Chapter 11 - Troubleshooting
Power on ProtectionFault
Prot PTC
Reset Back
Power on ProtectionFault
Prot SCR OL
Reset Back