Low Voltage Products & Systems 69
ABB Inc. 888-385-1221 www.abb-control.com AC 1006.9 - 5/03
Chapter 7 - Settings and configuration
Figure 14: Setting Ie menu
Figure 15: Confirming Setting Ie
Figure 16: Overload class
Figure 17: Confirming OL Class
Figure 18: Confirming OL Class
Figure 19: Confirming OL Class
Figure 20: Ready?/Tune Set menu
Setting Ie 100A
Store
Setting Ie 100A
Next Back
OL Class 10
Store
OL Class 10
Next Back
Ext ByPass Yes
Store
Ext ByPass Yes
Next Back
Ready?
Yes Tune Set
Setting I
e
(motor FLA)
Set the motor full load current (i.e. rated motor current if the
unit is connected In Line).
For units connected Inside Delta, the Setting I
e
must be set
according to the current in the delta circuit = 58% of
the rated motor current.
Press Store to save the data after setting the current.
Confirm the
Setting I
e
by pressing
Next
. If the wrong value is
set, press
Back
and set the correct value.
Overload class (OL Class)
Select the desired overload class. Available classes:
10
10A
20
30
Press
Store
to save the selected class.
Confirm the selected overload class by pressing
Next
. If the
wrong overload class was selected, press
Back
and select
the correct class.
External By-Pass contactor (Ext ByPass)
If an External Bypass contactor is used, set the parameter to
Yes
, otherwise select
No
.
Press
Store
to save the data.
Confirm the selection of external by-pass by pressing
Next
.
If the wrong selection was made, press
Back
and correct the
selection.
Tune Set
The configuration of the application setting menu is now
complete. If no tuning of the settings is desired, it is possible
to return to the top level by pressing
Yes
.
If tuning some parameters is desired, select
Tune Set
.
(1/( 3))