74 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 7 - Settings and configuration
Kick Start
Activate the
Kick Start
function by entering this menu. Press
Store
to save the selection.
Kick Level
Set the required level of the Kick Start. Press
Store
to save the
data.
This menu will only be visible if Kick Start is activated.
Kick Time
Set the required time for the kick start. Press
Store
to save the
data.
This menu will only be visible if Kick Start is activated.
Start Range
The ramp time for start can be set between 1 and 30 seconds as
default. If required, the range can be extended up to 120 seconds
by entering this menu. Press
Store
to save the data.
Stop Range
The ramp time for stop can be set between 0 and 30 seconds as
default. If required, the range can be extended up to 120 seconds
by entering this menu. Press
Store
to save the data.
The configuration of the parameters in the Start/Stop group is now
completed. It is possible to return to top level by pressing Back
three times. To configure the protections, proceed to that menu.