80 Low Voltage Products & Systems
AC 1006.9 - 5/03 ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 7 - Settings and configuration
Phase reversal (Phase Rev)
Activate the phase reversal protection if required by chang-
ing to
Yes
.
If Yes is selected, the following setting will be available:
Phase reversal type of operation (Ph Rev Op)
Select what operation should be initiated if the phase
reversal protection is activated:
Stop M The motor will stop and a manual reset is required.
Stop A The motor will stop and an automatic reset is
performed.
Ind Only indication will be given.
Press
Store
to save the selected operation.
PTC
Activate the PTC protection if required by changing to
Yes
.
If “Yes” is selected, the following setting will be avail-
able:
PTC type of operation (PTC Op)
Select what operation should be initiated if the PTC protec-
tion is activated:
Stop M The motor will stop and a manual reset is required.
Stop A The motor will stop and an automatic reset is
performed.
Ind Only indication will be given.
Press
Store
to save the selected operation.