Mode: The voltage and current used for the power measurement. The setting
possibilities are shown in table 34.
Table 34: Complex power calculation
Set value
Mode
Formula used for complex power calculation
A,B,C
* * *
A B C
A B C
S V I V I V I= × + × + ×
EQUATION2038 V1 EN-US (Equation 55)
Arone
* *
A C
AB BC
S V I V I= × ×-
EQUATION2039 V1 EN-US (Equation 56)
PosSeq
*
PosSeq
PosSeq
S 3 V I= × ×
EQUATION2040 V1 EN-US (Equation 57)
A,B
EQUATION2041 V1 EN-US (Equation 58)
B,C
EQUATION2042 V1 EN-US (Equation 59)
C,A
EQUATION2043 V1 EN-US (Equation 60)
A
EQUATION2044 V1 EN-US (Equation 61)
B
EQUATION2045 V1 EN-US (Equation 62)
C
EQUATION2046 V1 EN-US (Equation 63)
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
1MRK 505 370-UUS A Section 7
Current protection
Busbar protection REB670 2.2 ANSI 231
Application manual