of the CT is distorted and it might have severe effects on the performance of the
protection relay.
In practise, the actual accuracy limit factor (F
a
) differs from the rated accuracy limit
factor (F
n
) and is proportional to the ratio of the rated CT burden and the actual CT
burden.
The actual accuracy limit factor is calculated using the formula:
A071141 V1 EN
F
n
the accuracy limit factor with the nominal external burden S
n
S
in
the internal secondary burden of the CT
S the actual external burden
4.1.1.2  Non-directional overcurrent protection
The current transformer selection
Non-directional overcurrent protection does not set high requirements on the accuracy
class or on the actual accuracy limit factor (F
a
) of the CTs. It is, however,
recommended to select a CT with F
a
 of at least 20.
The nominal primary current I
1n
 should be chosen in such a way that the thermal and
dynamic strength of the current measuring input of the protection relay is not
exceeded. This is always fulfilled when
I
1n
 > I
kmax
 / 100,
I
kmax
 is the highest fault current.
The saturation of the CT protects the measuring circuit and the current input of the
protection relay. For that reason, in practice, even a few times smaller nominal
primary current can be used than given by the formula.
Recommended start current settings
If I
kmin
 is the lowest primary current at which the highest set overcurrent stage is to
operate, the start current should be set using the formula:
Current start value < 0.7 × (I
kmin
 / I
1n
)
I
1n
 is the nominal primary current of the CT.
The factor 0.7 takes into account the protection relay inaccuracy, current transformer
errors, and imperfections of the short circuit calculations.
Section 4 1MRS758127 C
Requirements for measurement transformers
94 RED615
Application Manual