As a consequence of sending interlocking information to remote end, also receiving of
same information locally is needed. Therefore, remote feeder ready, remote circuit
breaker open and remote current transformer failure are connected to the binary signal
transfer function outputs. The remote binary transfer output signal is connected to the
binary output X110:SO3.
BSTGGIO1
SEND_SIG_1
SEND_SIG_2
SEND_SIG_3
SEND_SIG_4
SEND_SIG_5
SEND_SIG_6
SEND_SIG_7
SEND_SIG_8
RECV_SIG_1
RECV_SIG_2
RECV_SIG_3
RECV_SIG_4
RECV_SIG_5
RECV_SIG_6
RECV_SIG_7
RECV_SIG_8
SEND_SIG_A
RECV_SIG_A
REMOTE_BINARY_TRANSFE
REMOTE_FEEDER_READYLOCAL_FEEDER_READY
CCSPVC1_FAIL
110_BI2_BINARY_TRANSFER
REMOTE_CB_OPEN
REMOTE_CCSPVC_FAIL
CBXCBR1_OPENPOS
BSTGGIO1_SEND_SIG_A
BSTGGIO1_RECV_SIG_A
GUID-7ACC6207-5896-4449-9E89-BAFA92A73010 V2 EN
Figure 35: Binary signal transfer function
3.3.3.4 Functional diagrams for control and interlocking
Two types of disconnector and earthing switch function blocks are available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information is connected to DCSXSWI1 and ESSXSI1.
DCSXSWI1
POSOP EN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
DCSXSWI1_OKPOS
X110_BI6_CB_TRUCK_IN_TEST
X110_BI5_CB_TRUCK_IN_SERVICE
GUID-F151A155-141D-4581-9218-30796B22E7F0 V1 EN
Figure 36: Disconnector 1 control logic
ESSXSWI1
POSOP EN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
ESSXSWI1_OPENPOSX110_BI8_ES1_OPENED
X110_BI7_ES1_CLOSED
GUID-8FF4B653-B8F2-4A83-AEB0-D0A371F8E7F1 V1 EN
Figure 37: Earth switch 1 control logic
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or circuit breaker truck and earth-switch position status, status of the trip
logics and remote feeder position indication. Master trip logic, disconnector and
earth-switch statuses are local feeder ready information to be sent for the remote end.
The OKPOS output from DCSXSWI defines if the disconnector or circuit breaker
truck is either open (in test position) or close (in service position). This, together with
the open earth-switch and non-active trip signals, activates the close-enable signal to
the circuit breaker control function block. The open operation for circuit breaker is
always enabled.
1MRS758127 C Section 3
RED615 standard configurations
RED615 53
Application Manual