Section 3 RED615 standard configurations
3.1 Standard configurations
RED615 is available with two alternative standard configurations. The standard
signal configuration can be altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the creation
of multi-layer logic functions utilizing various logical elements including timers and
flip-flops. By combining protection functions with logic function blocks the relay
configuration can be adapted to user specific application requirements.
The relay is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. Some of the supported functions in RED615 must be
added with the Application Configuration tool to be available in the Signal Matrix tool
and in the relay. The positive measuring direction of directional protection functions
is towards the outgoing feeder.
Table 9: Standard configurations
Description
Std. conf.
Line differential protection with non-directional earth-fault protection and circuit-breaker
condition monitoring
C
Line differential protection with directional overcurrent and earth-fault protection, voltage
and frequency based protection and measurements, synchro-check and circuit-breaker
condition monitoring (RTD option, optional power quality and fault locator)
D
Table 10: Supported functions
Function
IEC 61850 C D
Protection
Three-phase non-directional overcurrent protection, low stage PHLPTOC 1
Three-phase non-directional overcurrent protection, high stage PHHPTOC 2
Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1 1
Three-phase directional overcurrent protection, low stage DPHLPDOC 2
Three-phase directional overcurrent protection, high stage DPHHPDOC 1
Non-directional earth-fault protection, low stage EFLPTOC 2
Non-directional earth-fault protection, high stage EFHPTOC 1
Non-directional earth-fault protection, instantaneous stage EFIPTOC 1
Directional earth-fault protection, low stage DEFLPDEF 2
Directional earth-fault protection, high stage DEFHPDEF 1
Table continues on next page
1MRS758127 C Section 3
RED615 standard configurations
RED615 31
Application Manual