TPGAPC2
IN1
IN2
OUT1
OUT2
BACKUP_PROT_OPERATE_PULSEBACKUP_PROT_OPERATE
OR6
B1
B2
B3
B4
B5
B6
O
PDNSPTOC1_OPERATE
EFxPTOC_OPERATE
PHxPTOC_OPERATE
NSPTOC_OPERATE
BACKUP_PROT_OPERATE
GUID-E7E999CE-55E3-443A-95A2-4BF9339375AD V1 EN
Figure 56: Timer logic for backup protection operate pulse
3.3.3.8 Other functions
The configuration includes few instances of multipurpose protection MAPGAPC,
harmonics-based earth-fault protection, high-impedance fault detection function
PHIZ, runtime counter for machines and devices MDSOPT and few instances of
different types of timers and control functions. These functions are not included in
application configuration but they can be added based on the system requirements.
3.4 Standard configuration D
3.4.1 Applications
The standard configuration with directional overcurrent and directional earth-fault
protection, phase-voltage and frequency based protection is mainly intended for cable
feeder applications in distribution networks. The standard configuration for line
current differential protection includes support for in-zone transformers. The
configuration also includes additional options to select earth-fault protection based on
admittance, wattmetric or harmonic principle.
Standard configuration D is not designed for using all the available functionality
content in one relay at the same time. Frequency protection functions and third
instances of voltage protection functions must be added with the Application
Configuration tool. To ensure the performance of the relay, the user-specific
configuration load is verified with the Application Configuration tool in PCM600.
The protection relay with a standard configuration is delivered from the factory with
default settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the protection relay enables this configuration to be
further adapted to different primary circuit layouts and the related functionality needs
by modifying the internal functionality using PCM600.
1MRS758127 C Section 3
RED615 standard configurations
RED615 61
Application Manual