Binary output Description Connector pins
X110-SO4 - X110:23-24
X130-SO1 - X130:10-12
X130-SO2 - X130:13-15
X130-SO3 - X130:16-18
Table 14: Default connections for LEDs
LED Description
1 Line differential protection biased stage operate
2 Line differential protection instantaneous stage operate
3 Line differential protection is not available
4 Protection communication failure
5 Autoreclose in progress
6 Backup protection operate
7 Breaker failure operate
8 Disturbance recorder triggered
9 Current transformer failure or trip circuit or circuit breaker supervision alarm
10 Binary signal transfer receive
11 Binary signal transfer send
3.3.2.2 Default disturbance recorder settings
Table 15: Default disturbance recorder analog channels
Channel
Description
1 IL1
2 IL2
3 IL3
4 Io
5 -
6 -
7 -
8 -
9 -
10 -
11 -
12 -