Channel ID text Level trigger mode
26 CCBRBRF1 - trbu Level trigger off
27 LDPLDF1 - blkd2h Level trigger off
28 LNPLDF1 - prot not active Level trigger off
29 PHIPTOC1 - operate Level trigger off
DPHHPDOC1 - operate
DPHLPDOC1 - operate
DPHLPDOC2 - operate
30 NSPTOC1 - operate Level trigger off
NSPTOC2 - operate
31 INTRPTEF1 - operate Level trigger off
32 EFHPTOC1 - operate Level trigger off
33 DEFLPDEF1 - operate Level trigger off
WPWDE1 - operate
EFPADM1 - operate
DEFLPDEF2 - operate
WPWDE2 - operate
EFPADM2 - operate
DEFHPDEF1 - operate
WPWDE3 - operate
EFPADM3 - operate
34 PDNSPTOC1 - operate Level trigger off
35 T1PTTR1 - alarm Level trigger off
36 T2PTTR2 - alarm Level trigger off
37 PHPTOV - operate Level trigger off
38 ROVPTOV1 - operate Level trigger off
ROVPTOV2 - operate
PSPTUV1- operate
NSPTOV1 - operate
39 T1PTTR1 - operate Level trigger off
T2PTTR2 - operate
40 PHPTUV1 - operate Level trigger off
PHPTUV2 - operate
41 INRPHAR1 - blk2h Level trigger off
42 PCSITPC1 - alarm Level trigger off
43 CCSPVC1 - alarm Level trigger off
44 SEQSPVC - fusef 3ph Level trigger off
45 SEQSPVC - fusef u Level trigger off
46 X110-BI4 - CB spring charged Level trigger off
47 X110-BI3 - gas pressure alarm Level trigger off
Table continues on next page
Section 3 1MRS758127 C
RED615 standard configurations
66 RED615
Application Manual

Table of Contents