feeding upstream. For this purpose, the TRBU operate output signal is connected to the
binary output X100:PO2.
CCBRBRF1
BLOCK
START
POSCLOSE
CB_FAULT
CB_FAULT_AL
TRBU
TRRET
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
OR6
B1
B2
B3
B4
B5
B6
O
CCBRBRF1_TRBU
PHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
DEFHPDEF1_OPERATE
DEFLPDEF2_OPERATE
WPWDE2_OPERATE
WPWDE3_OPERATE
CCBRBRF1_TRRE
GUID-527012AF-B080-4E51-BF8C-5888C2C4C4EA V1 EN
Figure 76: Circuit breaker failure protection function
The operate signals from the protection functions are connected to the two trip logics:
TRPPTRC1 and TRPPTRC2. The output of these trip logic functions is available at
binary output X100:PO3 and X100:PO4. The trip logic functions are provided with a
lockout and latching function, event generation and the trip signal duration setting. If
the lockout operation mode is selected, binary input X110:BI1 can be assigned to
RST_LKOUT input of both the trip logic to enable external reset with a push button.
Section 3 1MRS758127 C
RED615 standard configurations
76 RED615
Application Manual