It is assumed that there is no external resistor in the circuit breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR1
BLOCK ALARM
TCSSCBR2
BLOCK ALARM
OR
B1
B2
O
TCSSCBR1_ALARM
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR2_ALARM
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR_ALARM
GUID-62930E10-32E5-4921-90A5-054F5549A863 V1 EN
Figure 85: Trip circuit supervision function
OR6
B1
B2
B3
B4
B5
B6
O
TRPPTRC2_TRIP
X120_BI3_CB_OPENED
TRPPTRC1_TRIP TCSSCBR_BLOCKING
GUID-9DE42D33-5655-4E55-A2F2-0637375ED830 V1 EN
Figure 86: Logic for blocking of trip circuit supervision
Protection communication supervision PCSITPC is used in the configuration to block
the operation of the line differential function. This way, the malfunction of the line
differential is prevented. The activation of binary signal transfer outputs during the
protection communication failure is also blocked. These are done internally without
connections in the configurations. The protection communication supervision alarm
is connected to the alarm LED 4, disturbance recorder and binary output X100:SO2.
PCSITPC1
OK
WARNING
ALARM
COMM
PCSITPC1_ALARM
GUID-58C48BE3-531B-44BE-A181-0E5F2CFDC098 V2 EN
Figure 87: Protection communication supervision function
1MRS758127 C Section 3
RED615 standard configurations
RED615 81
Application Manual