The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or circuit breaker truck and earth-switch position status, status of the trip
logics and remote feeder position indication. Master trip logic, disconnector and
earth-switch statuses are local feeder ready information to be sent for the remote end.
The OKPOS output from DCSXSWI defines if the disconnector or circuit breaker
truck is either open (in test position) or close (in service position). This, together with
the open earth-switch and non-active trip signals, activates the close-enable signal to
the circuit breaker control function block. The open operation for circuit breaker is
always enabled.
If REMOTE_FEEDER_READY information is missing, for
example, in case of protection communication not connected, it
disables the circuit breaker closing in the local protection relay.
CBXCBR1
POSOP EN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X120_BI3_CB_OPENED
X120_BI2_CB_CLOSED
CBXCBR1_ENA_CLOSE
CBXCBR1_EXE_CL
CBXCBR1_EXE_OP
CBXCBR1_BLK_CLOSE
FALSE
CBXCBR1_AU_OPEN
CBXCBR1_AU_CLOSE
CBXCBR1_OPENPOS
CBXCBR1_SELECTED
GUID-6C35F21A-59A7-4EA8-9A6B-6FF1195E2B9D V2 EN
Figure 91: Circuit breaker 1 control logic
Any additional signals required by the application can be connected
for opening and closing of circuit breaker.
OR
B1
B2
O
CB_CLOSE_COMMANDCBXCBR1_EXE_CL
DARREC1_CLOSE_CB
GUID-85700A51-C7A3-4CE2-82DD-BE499AED6BBA V1 EN
Figure 92: Signals for closing coil of circuit breaker 1
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMANDTRPPTRC1_TRIP
CBXCBR1_EXE_OP
DARREC1_OPEN_CB
GUID-BDEE048C-67D8-4979-B135-5CBEAE8EC89E V1 EN
Figure 93: Signals for opening coil of circuit breaker 1
1MRS758127 C Section 3
RED615 standard configurations
RED615 83