A .pcmi file can be imported only when the bay is selected in the
plant structure.
GUID-B1EC4574-7D16-420B-85A3-C2C9AFAE750E V1 EN
Figure 30: Importing IED configuration
2. In the Import dialog box, select the .pcmi file to be imported and click Open.
After importing, the IED object is created in the plant structure.
After the .pcmi file has been imported, the IP address, the name and the technical key
that correspond to the physical IED have to be changed.
4.4 Setting the IED IP address in a project
The IP address and subnet mask of the IED object in PCM600 must match the front
and rear port of the protection relay (physical IED) to which the PC is connected. The
IP address of the protection relay can only be set via the LHMI or Parameter Setting
tool in PCM600. The PC and protection relay need to be on the same subnet.
1MRS241255 B Section 4
Setting up a project
611 series 49
Engineering Manual