Station HMI
GW
cc
Station bus
breakers disconnectors earthing switches
IEC08000227.vsd
Apparatus
Control
IED
I/O
Local
HMI
Apparatus
Control
IED
I/O
Apparatus
Control
IED
I/O
Local
HMI
Local
HMI
IEC08000227 V1 EN
Figure 232: Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchrocheck
Pole discordance supervision
Operation counter
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks
designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Bay control QCBAY
Bay reserve QCRSV