EasyManua.ls Logo

ABB REG670 - Single-, Two- or Three-Phase Tripping

ABB REG670
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC05000545=4=en=Original.vsdx
BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
STDIR
TRIP
SMPPT RC
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
FW
REV
Phase segregated tri p L1, L2 and L3
from example line differential or
distance protection
Phase selection L1, L2 and L3 from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide a single pole trip
To activate lockout for any trip
To reset lockout
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
OR
To prepare 3 phase trip
for any trip signal
SMBRREC
PREP3P
TR3P
IEC05000545 V4 EN
Figure 302: The trip logic function SMPPTRC used for single-phase tripping
application
16.1.2.3 Single-, two- or three-phase tripping
The single-/two-/three-phase tripping mode provides single-phase tripping for single-
phase faults, two-phase tripping for two-phase faults and three-phase tripping for
three-phase faults. The operating mode is always used together with an autoreclosing
scheme with setting ARMode = 1/2/3 ph or ARMode = 1/2 ph.
The functionality is very similar to the single-phase scheme described above.
However, in addition to the connections for single phase above, SMBRREC must also
be informed that the trip is two phases by connecting the output TR2P to the input
TR2P in the SMBRREC function.
16.1.2.4 Lock-out
The SMPPTRC function block is provided with possibilities to initiate lock-out. The
lock-out can be set to only activate the block closing output CLLKOUT or initiate the
block closing output and also maintain the trip signal output TR3P (latched trip).
Section 16 1MRK 502 071-UEN -
Logic
602 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Table of Contents

Other manuals for ABB REG670

Related product manuals