Merging Unit
Bay level IED
XCBR
XCBR
XCBR
SCSWI
IEC 61850 on
station bus
XSWI
QCBAY
SCILO
SCSWI
GOOSEXLNRCV
SCILO
XLNPROXY
GOOSEXLNRCV XLNPROXY
-QA1
-QB1
-QB9
GOOSE over process bus
IEC16000070-1-EN.vsdx
IEC16000070 V1 EN
Figure 234: Signal flow between apparatus control functions with XCBR and
XSWI located in a breaker IED
Control operation can be performed from the local IED HMI. If users are defined in
the IED, then the local/remote switch is under authority control, otherwise the default
user can perform control operations from the local IED HMI without logging in. The
default position of the local/remote switch is on remote.
1MRK 502 071-UEN - Section 15
Control
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 499
Application manual