Over-Current
Total block via settings
Total block via configuration
Analog input error
Automatic block via settings
Automatic block via configuration
Under-Voltage
Command error
Position indication error
Tap changer error
Reversed Action
Circulating current
Communication error
Master-follower method
When the master is blocked, the followers will not tap by themselves and there is
consequently no need for further mutual blocking. On the other hand, when a follower
is blocked there is a need to send a mutual blocking signal to the master. This will
prevent a situation where the rest of the group otherwise would be able to tap away
from the blocked individual, and that way cause high circulating currents.
Thus, when a follower is blocked, it broadcasts a mutual block on the horizontal
communication. The master picks up this message, and blocks its automatic operation
as well.
Besides the conditions listed above for mutual blocking with the circulating current
method, the following blocking conditions in any of the followers will also cause
mutual blocking:
Master-follower out of position
Master-follower error (No master/More than one master)
General
It should be noted that partial blocking will not cause mutual blocking.
TR8ATCC, which is the “source” of the mutual blocking will set its AUTOBLK
output as well as the output which corresponds to the actual blocking condition for
example, IBLK for over-current blocking. The other TR8ATCCs that receive a
mutual block signal will only set its AUTOBLK output.
The mutual blocking remains until TR8ATCC that dispatched the mutual block signal
is de-blocked. Another way to release the mutual blocking is to force TR8ATCC,
which caused mutual blocking to Single mode operation. This is done by activating
the binary input SNGLMODE on TR8ATCC function block or by setting the
parameter OperationPAR to Off from the built-in local HMI or PST.
TR8ATCC function can be forced to single mode at any time. It will then behave
exactly the same way as described in section
"Automatic voltage control for a single
Section 15 1MRK 502 071-UEN -
Control
576 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual